The indoor unit fan stops. In addition, during hot starting, the
louvre stays at the horizontal position (angle C).
C. Cancelling
Hot starting will be cancelled when the temperature detected by
the indoor unit pipe temperature sensor is 18°C or higher, or
after a maximum 1 minute has passed since defrosting was
completed.
After cancellation, the “PREHEAT” display on the remote
control disappears and the louvre operation returns to the
previous setting.
(However, the indoor unit fan operates at LOW speed for 2
minutes after cancellation, and then returns to the previous
setting.)
<When hot start operation is cancelled by temperature>
<When hot start operation is cancelled by time>
27.6. Indoor unit fan control when thermostat is off during heating
mode operation
When the thermostat of the indoor unit turns off during heating mode operation, the indoor unit
fan operates for 2 minutes at LOW and then stops. In addition, 5 minutes after the thermostat of
the indoor unit turns off, the indoor unit fan operates at LOW for 10 seconds, and at 3 minutes
interval after that, it switches back to LOW operation for another 10 seconds.
141

Other manuals for Panasonic CS-A24BD2P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A24BD2P and is the answer not in the manual?

Panasonic CS-A24BD2P Specifications

General IconGeneral
BrandPanasonic
ModelCS-A24BD2P
CategoryAir Conditioner
LanguageEnglish

Related product manuals