3 FAN PERFORMANCE (Pages: 52 ~ 54)
Fan Performance Test Report
Model External static
pressure
Pa (mmAq)
Fan
speed
Current
(A)
Power
consumption
(kW)
RPM
(r/m)
Air volume
(m
3
/min)
98 (10) Hi 0.84 0.16 1396 18
CS-A24BD2P 79 (8.1) Me 0.56 0.11 1250 16
73 (7.5) Lo 0.51 0.10 1208 15
98 (10) Hi 0.80 0.17 1408 20
CS-A28BD2P 81 (8.5) Me 0.52 0.11 1281 18
72 (7.4) Lo 0.46 0.10 1208 17
98 (10) Hi 1.36 0.31 1225 35
CS-A34BD2P 75 (7.5) Me 1.07 0.23 1070 29
53 (5.4) Lo 0.87 0.18 904 24
98 (10) Hi 1.67 0.38 1370 40
CS-A43BD2P 81 (8.3) Me 1.31 0.31 1250 36.5
70 (7.2) Lo 1.18 0.28 1160 34
98 (10) Hi 2.44 0.49 1406 45
CS-A50BD2P 90 (9.2) Me 1.74 0.38 1350 43
79 (8.1) Lo 1.37 0.31 1265 40.5
●
●●
●
CS-A24BD2P
Fan Performance Curve
4