26.6. Excess heat dissipation for indoor unit
The indoor unit fan continues operating for 30 seconds after heating mode operation turns off
in order to / dissipate excess heat.
1. When heating mode operation has stopped / (LOW operation for
30 seconds)
2. When operation is set to a mode other than heating by means of
the OPERATION MODE switch
3. If operation starts again during the 30 seconds mentioned in (1)
above / (The fan operates at LOW speed for the remainder of the
30 seconds in (1), and then hot start commences.)
26.7. Defrost mode operation time chart
1. Start and completion of defrosting
A. Start / During heating mode operation (including automatic
heating), after the 45-minute defrosting cycle time has / passed,
defrosting starts if the temperature detected by the outdoor unit
heat exchanger outlet sensor is / 2~C or lower for a continuous