3. Cancelling / Hot starting is cancelled when the temperature
detected by the indoor unit pipe temperature sensor is 18~C / or
higher, or after a maximum 1 minute has passed since defrosting
was completed. / After cancellation, the "PREHEAT" display on
the remote control disappears and the louvre operation / returns
to the previous setting. / (However, the indoor unit fan operates
at LOW speed for 2 minutes after cancellation, and then returns to
/ the previous setting.) / < When hot start operation is cancelled
by temperature >
26.5. Indoor unit fan control when thermostat is off during heating
mode operation
When the thermostat of the indoor unit turns off during heating mode operation, the indoor unit
fan operates for 2 minutes at LOW and then stops. In addition, 5 minutes after the thermostat of
the indoor unit turns off, the indoor unit fan again runs at LOW for 10 seconds, and at 3-minute
intervals after that it switches back to LOW operation for 10 seconds.