8.5.9. Compressor Overload Protection Control
Outdoor Fan Control
If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor
heat exchanger temperature falls to 49°C.
Compressor high pressure protection
If the indoor heat exchanger becomes 65°C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
This is to reduce the pressure, as to reduce the indoor heat exchanger temp. Nevertheless, is to protect the compressor
from overload of too high temperature.
8.5.10. 4-Way Valve Control
4-way valve always on during Heating operation. (except deicing operation)
When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
This is to prevent the refrigerant flow process sound for being occur.
8.5.11. Outdoor Fan Motor Control
When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
This is to release the heat and to obtain the lowest pressure as fast as possible.
26
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A7DKD and is the answer not in the manual?

Panasonic CS-A7DKD Specifications

General IconGeneral
BrandPanasonic
ModelCS-A7DKD
CategoryAir Conditioner
LanguageEnglish

Related product manuals