– 17 –
MAC9512086C2
CS-C181KE
Operation Details
3) Air Circulation Mode Operation
When the temperature near the ceiling reaches the setting temperature, Air Circulation Mode operation commences
at low airflow volume. It stops when the temperature drops to 2°C below the setting temperature.
Air Circulation Mode Operation Time Diagram
ON
Setting
Temp.
OFF
Compressor
Indoor Fan
Outdoor Fan
Operation
Indication LED
2°C
Intake Air Temp.
a b c d e
Lo Lo
Operation
Stop
Cooling Mode
Soft Dry Mode
Setting Temperature (Standard)
25°C
22°C
Cooling Mode
Soft Dry Mode
23°C
Intake Air
Temperature
Cooling Mode
Soft Dry Mode
Setting Temperature (Standard)
27°C
24°C
Cooling
Soft Dry
25°C
Intake Air
Temperature
4) Automatic Mode Operation
Standard for Determining Operation Mode
(a) Indoor fan operates at Lo fan speed for 20 seconds.
(b) After judging indoor air temperature, the operation mode is determined and operation continued at the mode
determined.
(c) After the operation mode has been determined, the mode does not change. However, Soft Dry mode operation
includes Cooling mode operation.
(d) Room temperature adjustment.
The following are added to the setting temperature specified as above.
(e) If the value for R32 is changed to 47K (Normal 10K), the mode judging temperature and standard setting
temperature is increased by 2°C.
Cooling
27°C
25°C
23°C
Soft Dry
24°C
22°C
20°C
Higher +2°C
Standard ±0°C
Lower –2°C