12.4.5. Freeze Preventive Control
To protect indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form return to compressor.
This control will activate when the temperature of indoor heat exchanger falls below 2°C continuously for more than 4 minutes.
The current fan speed will change to freeze prevention speed after 70 seconds compressor on. When indoor pipe temperature
reaches certain temperature for 5 sec. the speed will be increased as in below figure.
Compressor will turn off when indoor temperature falls below 2°C for more than 4 minutes. It will restart again when indoor heat
exchanger temperature rises to 10°C.
Restart control (Time Delay Safety Control) will be applied in this control.
12.4.6. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically.
Time Delay Safety Control is activated before the compressor restart.
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.