8.1.14. Auto Restart Control
1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power
supply resumes.
2. This type of control is not applicable during ON/OFF Timer setting.
8.1.15. Indication Panel
LED POWER TIMER QUIET POWERFUL ION ALLERGEN
BUSTER
Color Green Orange Orange Orange Green Blue
Light ON Operation ON Timer Setting ON Quiet Mode ON Powerful Mode ON Ion Mode ON Operation ON
Light OFF Operation OFF Timer Setting OFF Quiet Mode OFF Powerful Mode OFF Ion Mode OFF Operation OFF
Note:
•
If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode
judgment, or delay ON timer sampling.
•
If Timer LED is blinking, there is an abnormality operation occurs.
•
If Ionizer, LED is blinking, there is an abnormality of Ionizer occurs.
8.1.16. Auto Operation Switch
1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
3. When the switch is pressed between 8 to 11 seconds, the unit will enter forced Heating Mode standby. Press timer decrement
button for 5S for the unit to operate in Heating Mode.
4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control (timer decrement button
for 5S), the unit can be changed to different controlling setting (4 type of transmission codes).
5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote control signal
receiving sound can be cancelled or turned on.
32
CS-E15DKEW CU-E15DKE / CS-E18DKEW CU-E18DKE / CS-E21DKES CU-E21DKE