EasyManua.ls Logo

Panasonic CS-E24CKE - Page 34

Panasonic CS-E24CKE
93 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.2.2.3. Anti-Freezing Control
1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3. At the same time, indoor fan speed increase +40 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
8.2.2.4. Anti-Dew Formation Control
a) Control 1
This control is perform if the following conditions is fulfilled during cooling/dry operation.
i. Control Start Condition
1) Indoor Intake Temperature 24°C & above
2) Outdoor Temperature Refer below
3) Remote Control Setting Temperature 16°C & above, below 30°C
4) Fan tab Refer below
Control start after 1) ~ 4) continued for more than 1 minutes.
ii. Control Contents
* If the outdoor temperature
30°C
Me & above (include auto air flow)
0 T<30min 74
30 min T<90min 67
90 min T < 420 min 67
0 T<30min 67
30 min T<90min 54
90 min T < 420 min 54
34
CS-E24CKE CU-E24CKE

Table of Contents

Related product manuals