8.2.2.3. Anti-Freezing Control
1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3. At the same time, indoor fan speed increase +40 rpm compared to its normal operation.
4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
8.2.2.4. Anti-Dew Formation Control
a) Control 1
This control is perform if the following conditions is fulfilled during cooling/dry operation.
i. Control Start Condition
1) Indoor Intake Temperature 24°C & above
2) Outdoor Temperature Refer below
3) Remote Control Setting Temperature 16°C & above, below 30°C
4) Fan tab Refer below
Control start after 1) ~ 4) continued for more than 1 minutes.
ii. Control Contents
* If the outdoor temperature
30°C
Me & above (include auto air flow)
0 T<30min 74
30 min T<90min 67
90 min T < 420 min 67
0 T<30min 67
30 min T<90min 54
90 min T < 420 min 54
34
CS-E24CKE CU-E24CKE