Outdoor Temp. (°C)
Indoor wet
bulb temp.
30 35 40 46
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0°C 6.75 5.11 2.21 6.30 4.90 2.37 5.86 4.71 2.54 5.33 4.48 2.74
19.0°C 6.80 2.41
19.5°C 7.41 5.35 2.25 6.92 5.14 2.42 6.44 4.95 2.59 5.85 4.71 2.79
22.0°C 8.07 5.55 2.29 7.54 5.34 2.46 7.02 5.15 2.63 6.38 4.91 2.84
TC - Total Cooling Capacity (kW) Indoor 27°C/19°C
SHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°C
IP - Input Power (kW)
78