Drain Hose
Inner Diameter mm 16.7
Length mm 650
Indoor Heat
Exchanger
Fin Material Aluminium (Pre Coat)
Fin Type Slit Fin
Row x Stage x FPI 2 x 15 x 21
Size (W x H x L) mm 610 x 315 x 25.4
Outdoor
Heat
Exchanger
Fin Material Aluminium (Blue Coated)
Fin Type Corrugated Fin
Row x Stage x FPI 2 x 28 x 17
Size (W x H x L) mm 36.4 x 588 x 606.6
Air Filter
Material Polypropelene
Type One-touch
Power Supply Outdoor Power Supply
Power Supply Cord A Nil
Thermostat Electronic Contol
Protection Device Electronic Contol
DRY BULB WET BULB
Indoor
Operation
Range
Cooling
Maximum °C 32 23
Minimum °C 16 11
Heating
Maximum °C 30 -
Minimum °C 16 -
Outdoor
Operation
Range
Cooling
Maximum °C 46 26
Minimum °C 5 4
Heating
Maximum °C 24 18
Minimum °C -15 -16
1. Cooling capacities are based on indoor temperature of 27°C DRY BULB (80.6°F DRY BULB), 19.0°C WET BULB (66°F WET BULB) and
outdoor air temperature of 35°C DRY BULB (95°F DRY BULB), 24°C WET BULB (75.2°F WET BULB)
2. Heating capacities are based on indoor temperature of 20°C Dry Bulb (68°F Dry Bulb) and outdoor air temperature of 7°C Dry Bulb (44.6°F
Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb)
3. Heating low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor 2/1°C
4. Heating extreme low temperature capacity, Input Power and COP measured at 230 V, indoor temperature 20°C, outdoor -7/-8°C
5. Specifications are subjected to change without prior notice for further improvement.