Multi Split Combination Possibility:
o A single outdoor unit enables air conditioning of up to two separate rooms for CU-2E15PBE, CU-2E18PBE.
o A single outdoor unit enables air conditioning of up to three separate rooms for CU-3E18PBE.
o A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E23PBE.
o A single outdoor unit enables air conditioning of up to four separate rooms for CU-4E27PBE.
o A single outdoor unit enables air conditioning of up to five separate rooms for CU-5E34PBE.
CONNECTABLE
INDOOR UNIT
OUTDOOR UNIT
CU-2E15PBE CU-2E18PBE CU-3E18PBE CU-4E23PBE
Type/ROOM A B A B A B C A B C D
Wall
1.6kW CS-ME5PKE
2.0kW
CS-E7PKEW
CS-XE7PKEW
2.5kW
CS-E9PKEW
CS-XE9PKEW
CS-ME9PD3EA
CS-ME9PB4EA
CS-E9GFEW
CS-E9GFEW-2
CS-E9PD3EA
CS-E9PB4EA
3.2kW
CS-E12PKEW
CS-XE12PKEW
CS-ME12PD3EA
CS-ME12PB4EA
CS-E12GFEW
CS-E12GFEW-2
CS-E12PD3EA
CS-E12PB4EA
4.0kW
CS-E15PKEW
CS-XE15PKEW
– – – –
5.0kW
CS-E18PKEW
CS-XE18PKEW
CS-ME18PD3EA
CS-ME18PB4EA
CS-E18GFEW
CS-E18GFEW-2
– – – –
6.0kW
CS-E21PKEW
CS-XE21PKEW
CS-ME21PB4EA
– – – –
Capacity range of connectable
indoor units
From 3.2kW
to 5.6kW
From 3.2kW
to 6.4kW
From 4.5kW
to 9.0kW
From 4.5kW
to 11.0 kW
Pipe length
1 room maximum
pipe length (m)
20 20 25 25
Allowable elevation (m) 10 10 15 15
Total allowable pipe
length (m)
30 30 50 60
Total pipe length for
maximum chargeless
length (m)
20 20 30 30
Additional gas
amount over
chargeless length (g/m)
15 15 20 20
Note: “” : Available
Remarks for CU-2E15PBE / CU-2E18PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-2E15PBE.
(Total nominal capacity of indoor units is between 3.2kW to 5.6kW)
1) Two CS-E7PKEW only (Total nominal cooling capacity is
4.0kW)
2) One CS-E7PKEW and one CS-E9PKEW. (Total nominal cooling capacity is 4.5kW)
Remarks for CU-3E18PBE / CU-4E23PBE
1. At least two indoor units must be connected.
2. The total nominal cooling capacity of indoor units that will be connected to outdoor unit must be within
connectable capacity range of indoor unit. (as shown in the table above)
Example: The indoor units’ combination below is possible to connect to CU-3E18PBE.
(Total nominal capacity of indoor units is between 4.5kW to 9.0kW)
1) Two CS-E9PKEW only (Total nominal cooling capacity is 5.0kW)
2) Three CS-E12PKEW. (Total nominal cooling capacity is 9.6kW)