EasyManua.ls Logo

Panasonic CS-E9PB4EA - Page 70

Panasonic CS-E9PB4EA
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70
Diagnosis
display
Abnormality /
Protection control
Abnormality
Judgment
Protection
Operation
Problem Check location
F95
Outdoor cooling high
pressure protection
4 times happen
within 20 minutes
Cooling high pressure
protection
Check refrigeration system
Outdoor air circuit
F96
Power transistor
module overheating
protection
4 times happen
within 30 minutes
Power transistor module
overheat
PCB faulty
Outdoor air circuit (fan motor)
F97
Compressor
overheating
protection
3 times happen
within 30 minutes
— Compressor overheat
Insufficient refrigerant
F98
Total running current
protection
3 times happen
within 20 minutes
— Total current protection
Check refrigeration system
Power source or compressor
lock
F99
Outdoor direct
current (DC) peak
detection
Continuous
happen for 7 times
Power transistor module
current protection
Power transistor module faulty
or compressor lock

Table of Contents

Other manuals for Panasonic CS-E9PB4EA

Related product manuals