9.7.3. Powerful Control
 • To achieve setting temperature quickly.
 • Cooling powerful operation:
 − Setting temperature and thermostat shifting temperature are decrease by 2°C (lower limit 16°C).
 − Airflow direction is optimized regardless the air flow setting at remote control.
 − Fan speed is optimized at Hi regardless the fan speed setting at remote control.
 • Drying powerful operation:
 − Setting temperature and thermostat shifting temperature are decrease by 2°C (lower limit 16°C).
 − Airflow direction follows remote control setting.
 • Heating powerful operation:
 − Setting temperature and thermostat shifting temperature are increase by 2°C (upper limit 31°C).
 − Airflow direction is optimized regardless the air flow setting at remote control.
 − Fan speed is optimized at Hi regardless the fan speed setting at remote control.
 • During powerful operation, the powerful indicator lights on.
 • Powerful operation cancel when:
 − Powerful operates for more than 15 minutes.
 − Powerful button is pressed again.
 − Operation mode changed.
 − Operation stopped by remote control or emergency button.
 − OFF timer is activated.
9.7.4. Hot Start Control
 • Hot start control operates at the starting of heating operation, where [PREHEAT] displayed at wired remote control.
 • Indoor fan stops until hot start control ends (indoor heat exchanger temperature increases or 4 minutes past heating operation
starts), fan control resume.
9.7.5. Energy Save Control
 • During Cooling Operation, press "Economy" button at remote control to enable Energy Saving Operation.
 • The air conditioner judges the stable condition, where the different between indoor suction temperature and setting temperature
is 1°C for 30 minutes and moderately shifts the set temperature in 0.5°C steps (Maximum 2°C) to control energy saving
operation.
 • If temperature different is out of range, energy save operation will not start.
 • Energy Save Operation is canceled by pressing the "Economy" button again.
Energy save control time chart