9.7.9. Time Delay Safe Control
 • The compressor will not start for three minutes after stop of operation.
9.7.10. Outdoor Fan Remaining Heat Removal Control
 • When compressor stops, outdoor fan operates at High speed for 1 minute to remove the remaining heat.
9.7.11. Crank Case Heater Control
 • Crank case heater ON when the compressor is shutdown and discharge temperature is 20°C to prevents the refrigerant solving
into compressor oil inside the compressor shell at cold condition.
9.7.12. Pump Down
 • To enable pump down operation, at outdoor PCB, set the DS1 and DS2 to OFF position.
 • Press Test Run button for 1 second. SW1 located at outdoor printed circuit board.
 • During Pump Down operation, push the Test Run button again for 1 second to stop the pump down operation.
 • The pump down operation runs for 10 minutes.
9.8. Protection control
9.8.1. Outdoor Low-pressure Protection Control
 • The purpose of low-pressure protection control is gas leakage detection control.
 • The low-pressure protection control starts when low-pressure switch is activated less than 15 minutes after compressor startup.
During heating operation or deice control low-pressure detection does not start.
 • During this protection control, compressor is shut down, indoor unit is set to thermo-off status.
 • After 6 occasions, suction pressure error is displayed; all operations stopped except outdoor fan remaining heat removal
control.