8
• 
Any part of refrigerating circuit 
(evaporators, air coolers, AHU, 
condensers or liquid receivers) or 
piping should not be located in the 
proximity of heat sources, open 
fl ames, operating gas appliance or 
an operating electric heater.
• 
The user/owner or their authorised 
representative shall regularly check 
the alarms, mechanical ventilation 
and detectors, at least once a 
year, where as required by national 
regulations, to ensure their correct 
functioning.
• 
A logbook shall be maintained. The 
results of these checks shall be 
recorded in the logbook.
• 
In case of ventilations in occupied 
spaces shall be checked to confi rm 
no obstruction.
• 
Before a new refrigerating system 
is put into service, the person 
responsible for placing the system 
in operation should ensure that 
trained and certifi ed operating 
personnel are instructed on the 
basis of the instruction manual 
about the construction, supervision, 
operation and maintenance of the 
refrigerating system, as well as the 
safety measures to be observed, 
and the properties and handling of 
the refrigerant used.
• 
The general requirement of 
trained and certifi ed personnel are 
indicated as below:
a) Knowledge of legislation, 
regulations and standards 
relating to fl ammable 
refrigerants; and,
b) Detailed knowledge of and 
skills in handling fl ammable 
refrigerants, personal protective 
equipment, refrigerant 
leakage prevention, handling 
of cylinders, charging, leak 
detection, recovery and 
disposal; and,
c) Able to understand and to apply 
in practice the requirements 
in the national legislation, 
regulations and Standards; and,
d) Continuously undergo regular 
and further training to maintain 
this expertise.
1.  Installation (Space)
• 
Product with fl ammable 
refrigerants, shall not be installed in 
an unventilated space, if that space 
is smaller than Amin (m²).
• 
In case of fi eld charge, the effect 
on refrigerant charge caused by 
the different pipe length has to be 
quantifi ed, measured and labelled.
• 
Must ensure the installation of pipe-
work shall be kept to a minimum. 
Avoid use dented pipe and do not 
allow acute bending.
• 
Must ensure that pipe-work shall be 
protected from physical damage.
• 
Must comply with national gas 
regulations, state municipal rules 
and legislation. Notify relevant 
authorities in accordance with all 
applicable regulations.
• 
Must ensure mechanical 
connections be accessible for 
maintenance purposes.
• 
In cases that require mechanical 
ventilation, ventilation openings 
shall be kept clear of obstruction.
• 
When disposal of the product, do 
follow to the precautions in #12 and 
comply with national regulations.
Always contact to local municipal 
offi ces for proper handling.