17.3. Self Diagnosis Function
The display screen of wireless remote control unit and the self-diagnosis LEDs (green) on the outdoor printed circuit board in the
outdoor unit can be used to identify the location of the problem.
Refer to the table below to identify and solve the cause of the problem, and then re-start the air conditioner system.
If the problem is solved and operation returns to normal.
LED 1 illuminates and others LED are off.
LED 6LED 5LED 4LED 3LED 2LED 1
Abnormality
judgement
Protection
operation
Problem Check location
Diagnosis
display
Abnormality
or
protection
control
H11 Indoor/outdoor
abnormal
communication
After
operation for
1 minute
Indoor fan only
operation can
start by
entering into
force cooling
operation
Indoor/outdoor
communication not
establish
Indoor/outdoor
wire terminal
Indoor/outdoor
PCB
Indoor/outdoor
connection wire
H12 Indoor unit
capacity
unmatched
90s after
power supply
Total indoor
capability more than
maximum limit or
less than minimum
limit, or number of
indoor unit less than
two.
Indoor/outdoor
connection wire
Indoor/outdoor
PCB
Specification and
combination table
in catalogue
H14 Indoor intake
air temperature
sensor
abnormality
Continuous
for 5s
Indoor intake air
temperature sensor
open or short circuit
Indoor intake air
temperature
sensor lead wire
and connector
H15 Compressor
temperature
sensor
abnormality
Continuous
for 5s
Compressor
temperature sensor
open or short circuit
Compressor
temperature
sensor lead wire
and connector
H16 Outdoor
current
transformer
(CT)
abnormality
Current transformer
faulty or compressor
faulty
Outdoor PCB
faulty or
compressor
faulty
H19 Indoor fan
motor
merchanism
lock
Continuous
happen for 7
times
Indoor fan motor lock
or feedback
abnormal
Fan motor lead
wire and
connector
Fan motor lock or
block
H23 Indoor heat
exchanger
temperature
sensor
abnormality
Continuous
for 5s
Indoor heat
exchanger
temperature sensor
open or short circuit
Indoor heat
exchanger
temperature
sensor lead wire
and connector
H27 Outdoor air
temperature
sensor
abnormality
Continuous
for 5s
Outdoor air
temperature sensor
open or short circuit
Outdoor air
temperature
sensor lead wire
and connector
H28 Outdoor heat
exchanger
temperature
sensor 1
abnormality
Continuous
for 5s
Outdoor heat
exchanger
temperature sensor 1
open or short circuit
Outdoor heat
exchanger
temperature
sensor 1 lead
wire and
connector
H32 Outdoor heat
exchanger
temperature
sensor 2
abnormality
Continuous
for 5s
Outdoor heat
exchanger
temperature sensor 2
open or short circuit
Outdoor heat
exchanger
temperature
sensor 2 lead
wire and
connector