11 Installation Instruction
11.1. Select The Best Location
11.1.1. Indoor Unit
Do not install the unit in excessive oil fume area such as
kitchen, workshop and etc.
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
Recommended installation height for indoor unit shall be at
least 2.5 m.
11.1.2. Outdoor Unit
If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
There should not be any animal or plant which could be
affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
Do not place any obstacles which may cause a short circuit
of the discharged air.
If piping length is over 7.5 m, additional refrigerant should be
added as shown in the table.
Example: For PC36
If the unit is installed at a 10m distance, the quantity of
additional refrigerant should 75g ...... (10 - 7.5) m x 40 g/m
= 100 g
11.2. Indoor/Outdoor Unit
Installation Diagram
This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
Model
Piping size Rated
Length
(m)
Max.
Elevation
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Additional
Refrigerant
(g/m)
Gas Liquid
PC30 5/8” 3/8” 5 20 3 30 30
PC36 3/4” 3/8” 5 20 3 30 40