63
14.3 Error Code Table
Diagnosis
display
Abnormality / Protection control Abnormality Judgment
Emergency
Operation
Primary location to verify
H00 No abnormality detected - Normal operation
H11 Indoor / Outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
Internal / external cable connection
Indoor / outdoor PCB
H12 Connection capability rank abnormality Continuously for 90 sec
after power supplied
- -
H14 Indoor intake air temperature sensor
abnormality
Continue for 5 sec. -
Intake air temperature sensor
(defective or disconnected)
H15 Outdoor compressor temperature sensor
abnormality
Continue for 5 sec. -
Compressor temperature sensor
(defective or disconnected)
H16 Outdoor current transformer open circuit - -
Outdoor PCB
IPM (Power transistor) module
H19 Indoor fan motor mechanism locked 7 occurrences
continuously
-
Indoor PCB
Fan motor
H23 Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec. ○
Heat exchanger temperature sensor
(defective or disconnected)
H27 Outdoor air temperature sensor
abnormality
Continue for 5 sec. ○
Outdoor temperature sensor
(defective or disconnected)
H28 Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec. ○
Outdoor heat exchanger
temperature sensor (defective or
disconnected)
H33 Indoor / outdoor wrong connection - -
Indoor / outdoor supply voltage
H38 Indoor / outdoor mismatch (brand code) - - -
H98 Indoor temperature rise abnormality - -
Air filter dirty
Air circulation short circuit
H99 Indoor heat exchanger freeze prevention
protection
- -
Insufficient refrigerant
Air filter dirty
F11 4 way valve switching failure * 4 occurrences within 30
minutes
-
4-way valve
v-coil
F90 System and compressor microcomputer
communication error(for S10*** only)
2 occurrences within 5
seconds
-
Compressor
Outdoor PCB
F90 Power factor correction abnormality 4 occurrences within 20
minutes
-
Outdoor PCB
F91 Refrigerant cycle abnormal 2 occurrences within 20
minutes
-
No refrigerant ( 3-way valve is
closed)
F93 Outdoor compressor abnormal revolution 4 occurrences within 20
minutes
-
Outdoor compressor
F95 Cooling high pressure protection 4 occurrences within 20
minutes
-
Outdoor refrigerant circuit
F96 Intelligent power transistor overheating
protection
F97 Compressor temperature rise protection
control
- -
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
F98 Total running current protection 4 occurrences within 20
minutes
-
Insufficient refrigerant
Improper heat radiation
F99 Outdoor direct current (DC) peak
detection
7 occurrences
continuously
-
Outdoor PCB
IPM (Power transistor)
Compressor
Note:
“○” – Frequency measured and fan speed fixed
“ * ”– For cooling only model, it is the indication when indoor heat exchanger sensor or indoor air intake sensor has
abnormality.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep”
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one “beep” to four “beep” sounds.