14.4.19    F91 (Refrigeration Cycle Abnormality) 
Malfunction Decision Conditions 
•  During cooling, compressor frequency = Fcmax. 
•  During cooling and heating operation, running current: 0.65A < I < 1.65A. 
•  During cooling, indoor intake - indoor pipe < 4°C. 
 
Malfunction Caused 
•  Refrigerant shortage (refrigerant leakage) 
•  Poor compression performance of compressor. 
•  2/3 way valve closed. 
•  Detection error due to faulty indoor intake air or indoor pipe temperature sensors. 
 
Troubleshooting