14.4.21    F95 (Cooling High Pressure Abnormality) 
Malfunction Decision Conditions 
During operation of cooling, when outdoor unit heat exchanger high temperature data (61°C) is detected by the 
outdoor pipe temperature sensor. 
 
Malfunction Caused 
•  Outdoor pipe temperature rise due to short circuit of hot discharge air flow. 
•  Outdoor pipe temperature rise due to defective of outdoor fan motor. 
•  Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor. 
•  Outdoor pipe temperature rise due to defective outdoor unit PCB. 
 
Troubleshooting