10.1.7 Connect the Cable to the Indoor Unit
1 The inside and outside connection cable can be connected without removing the front grille.
2 Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x 1.5
mm
2
(1.0 ~ 1.5HP) or 4 x 2.5 mm
2
(2.0 ~ 2.5HP) flexible cord, type designation 60245 IEC 57 or heavier cord.
Do not use joint connection cable. Replace the wire if the existing wire (from concealed wiring, or otherwise)
is too short.
o Secure the connection cable onto the control board with the holder.
Note:
Isolating Devices (Disconnecting means) should have minimum 3.0 mm contact gap.
Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than the other AC wires as shown in the figure for the
electrical safety in case of the slipping out of the cord from the anchorage.