Panasonic CS-XE9CKE - Page 49

Panasonic CS-XE9CKE
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Freeze-up prevention, vacuum pump continuous running control
•
• •
• Avoid freeze-up in tube by vacuum pump continuous running at low outdoor temp.
•
• •
• Start condition
a. OD temp status 1(a,b)
b. O
2
supply level 0
•
• •
• Control content
a. Continuous running disregard of oxygen supply level
•
• •
• Cancellation condition
−
− −
− Start condition not fulfilled
•
• •
• Exceptional condition
During deice & MOPMPS08 after deice, OD temp. status does not update as the OD fan is stop. (Air temp. detection
disable).
3. Freeze-up prevention, 2 way valve control
•
• •
• Open valve periodically to prevent freeze-up during low OD air temp.
•
• •
• Open valve duration change according to air temp. status (1a or 1b).
a. Start condition
Either one of below condition is fulfilled.
i. O
2
supply leve 0 & OD air temp status shift to 1(a,b).
49
CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKE