 Safety Precautions
2-2.  Work
• 
Prior to beginning work on systems 
containing fl ammable refrigerants, 
safety checks are necessary to 
ensure that the risk of ignition 
is minimised. 
For repair to the 
refrigerating system, the precautions in 
#2-2 to #2-8 must be followed before 
conducting work on the system.
• 
Work shall be undertaken under 
a controlled procedure so as to 
minimize the risk of a fl ammable gas 
or vapour being present while the 
work is being performed.
• 
All maintenance staff and others 
working in the local area shall be 
instructed and supervised on the 
nature of work being carried out.
• 
Avoid working in confi ned spaces. 
Always ensure away from source, at 
least 2 meter of safety distance, or 
zoning of free space area of at least 
2 meter in radius.
• 
Wear appropriate protective 
equipment, including respiratory 
protection, as conditions warrant.
• 
Keep all sources of ignition and hot 
metal surfaces away.
2-3.  Checking for presence of 
refrigerant
• 
The area shall be checked with an 
appropriate refrigerant detector prior 
to and during work, to ensure the 
technician is aware of potentially 
fl ammable atmospheres.
• 
Ensure that the leak detection 
equipment being used is suitable for 
use with fl ammable refrigerants, i.e. 
non sparking, adequately sealed or 
intrinsically safe.
• 
In case of leakage/spillage 
happened, immediately ventilate 
area and stay upwind and away 
from spill/release.
• 
In case of leakage/spillage 
happened, do notify persons down 
wind of the leaking/spill, isolate 
immediate hazard area and keep 
unauthorised personnel out.
2-4.  Presence of fi re extinguisher
• 
If any hot work is to be conducted 
on the refrigerating equipment or 
any associated parts, appropriate 
fi re extinguishing equipment shall be 
available at hand.
• 
Have a dry powder or CO
2
 fi re 
extinguisher adjacent to the 
charging area.
2-5.  No ignition sources
• 
No person carrying out work in 
relation to a refrigerating system 
which involves exposing any pipe 
work that contains or has contained 
fl ammable refrigerant shall use any 
sources of ignition in such a manner 
that it may lead to the risk of fi re 
or explosion. He/She must not be 
smoking when carrying out such 
work.
• 
All possible ignition sources, 
including cigarette smoking, should 
be kept suffi ciently far away from 
the site of installation, repairing, 
removing and disposal, during which 
fl ammable refrigerant can possibly 
be released to the surrounding 
space.
• 
Prior to work taking place, the area 
around the equipment is to be 
surveyed to make sure that there 
are no fl ammable hazards or ignition 
risks.
• 
“No Smoking” signs shall be 
displayed.
2-6.  Ventilated area
• 
Ensure that the area is in the open 
or that it is adequately ventilated 
before breaking into the system or 
conducting any hot work.
• 
A degree of ventilation shall continue 
during the period that the work is 
carried out.
• 
The ventilation should safely 
disperse any released refrigerant 
and preferably expel it externally 
into the atmosphere.