Note:
” - Frequency measured and fan speed fixed.
F93 Outdoor compressor abnormal
revolution
4 times occurrences
within 20 minutes
Compressor
F95 Cooling high pressure protection 4 times occurrences
within 20 minutes
Outdoor refrigerant cycle
F96 IPM (power transistor) overheating
protection
Express refrigerant
Improper heat radiation
Outdoor PCB
F97 Outdoor compressor overheating
protection
4 times occurrences
within 10 minutes
Insufficient refrigerant
Compressor
F98 Total running current protection 3 times occurrences
within 20 minutes
Excess refrigerant
Improper heat radiation
F99 Outdoor direct current (DC) peak
detection
7 times occurrences Outdoor PCB
Compressor
Abnormality
judgement
Emergency
operation
Primary location to verify
Diagnosis
display
Abnormality or protection control