12.6. Self-diagnosis error code table
• The display screen on the wired remote control unit and the self-diagnosis LEDs (green) on the outdoor unit printed circuit board
in the outdoor unit can be used to indicate where the location of a problem is.
Refer to the table below to remove the cause of the problem, and then re-start the air conditioner system.
• If the problem disappears and operation returns to normal, the CHECK display on the remote control unit will switch off, but the
self-diagnosis LED will remain illuminated until operation is resumed.    ... illuminated. 
Wired remote 
control unit display
Outdoor unit printed circuit board 
LED
Location or problem Check location
Abnormal 
display
Detail 
display
2345678
F15 -01 Drain level Float switch problem Drain pump and drain pipe, indoor unit 
connectors CN-DRMTR&CN-TH2
F16 -01 Louver switch problem Louver motor, decorative panel connection 
terminal, or indoor unit louver motor 
connectors
F17 -02 D.C. Fan motor problem Indoor unit D.C.Fan motor or connection 
terminals
F20 -01 Indoor temperature sensor 
problem
Indoor temperature sensor lead wire or indoor 
unit connector or CN-TH2
-02 Remote control thermistor 
problem
Remote control thermistor
F21 -01 Pipe temp. sensor problem 
(indoor unit)
Pipe temperature sensor lead wire or indoor 
unit connector CN-TH1
F26 -01 Remote control transmission 
problem
Remote control unit cable and connection 
terminals
F27 -01 Indoor/outdoor unit 
disconnection problem
Indoor/outdoor unit connection cable and 
connection terminals, or indoor unit and 
outdoor unit power supplies (indoor side)
-05 Indoor/outdoor unit connection 
error problem
Indoor/outdoor unit connection wire (indoor 
side)
-01 Indoor/outdoor unit 
disconnection problem
Indoor/outdoor unit connection cable and 
connection terminals, or indoor unit and 
outdoor unit power supplies (outdoor side)
-05 Indoor/outdoor unit connection 
problem
Indoor/outdoor unit connection wire (outdoor 
side)
F30 -01 System problem Total capacity for the number of indoor units is 
insufficient, or over check the total capacity 
and the number of indoor units
-02 Open phase, or reversed phase 
of supply
Check the main power supply terminal board 
connections, or switch over any two of the 
power supply wires.
F31 -01 Suction pressure protection Insufficient refrigerant
-02 High-pressure cut-off Check the Refrigeration system
-06 4 way valve information Check the 4 way valve or lead wire
-10 Refrigerant system problem Insufficient refrigerant or valve operation 
(closed)
F32 -05 Compressor overcurrent 
protection
Open phase or lock in compressor
-06 Compressor discharge temp. 
protection
Insufficient refrigerant
F40 -21 Heat exchanger outlet 
temperature sensor problem
Heat exchanger outlet temperature sensor 
(COND TEMP) lead wire, connector CN-TH1
-51 Compressor discharge 
temperature sensor problem
Compressor discharge temperature sensor 
(DIS T. TEMP) lead wire, connector CN-DIS
F41 -02 High pressure switch open circuit 
problem
High-pressure switch lead wire, connector 
CN-PSW1
-12 Low pressure sensor problem Low pressure sensor lead wire, connector
F42 -11 Current detector open circuit Outdoor unit P.C. B (NOISE FILTER) fault or 
connector ACN2