EasyManua.ls Logo

Panasonic CU-E12NKE - Page 94

Panasonic CU-E12NKE
189 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
94
16.1.1 Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode Heating Mode
Condition of the
air conditioner
Low Pressure High Pressure
Electric current
during operation
Low Pressure High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Ô Ô Ô Ô Ô Ô
Clogged capillary tube or
Strainer
Ô Ô Ô Ò Ò Ò
Short circuit in the indoor unit
Ô Ô Ô Ò Ò Ò
Heat radiation deficiency
of the outdoor unit
Ò Ò Ò Ô Ô Ô
Inefficient compression
Ò Ô Ô Ò Ô Ô
• Carry out the measurement of pressure, electric current, and temperature fifteen minutes after an operation is started.

Table of Contents

Other manuals for Panasonic CU-E12NKE

Related product manuals