14.4.21 F98 (Input Over Current Detection)
Malfunction Decision Conditions
During cooling and heating operation, when an input over-current (X value in Total Running Current Control) is
detected by checking the input current value being detected by current transformer (CT) with the compressor running.
Malfunction Caused
Over-current due to compressor failure.
Over-current due to defective outdoor unit PCB.
Over-current due to defective inverter main circuit electrolytic capacitor.
Over-current due to excessive refrigerant.
Troubleshooting
60