4.2.1. Cooling.
CW-A180ES CW-A240ES
Item Pressure
(MPa)
Temperature
(°C)
Pressure
(MPa)
Temperature
(°C)
A 2.83 ~ 2.93 76 ~ 92 2.79 ~ 2.89 84 ~ 100
B 2.73 ~ 2.83 55 ~ 65 2.69 ~ 2.79 56 ~ 66
C 0.64 ~ 0.70 12 ~ 16 0.58 ~ 0.67 10 ~ 14
D 0.59 ~ 0.65 8~16 0.50 ~ 0.56 8~16
Note: Indoor temperature at 27°C (DB), 19°C (WB) and Outdoor at
35°C (DB), 24°C (WB) for Cooling.
4.1.1. Cooling.
CW-C180ES & CW-SC180ES CW-C240ES
Item Pressure
(MPa)
Temperature
(°C)
Pressure
(MPa)
Temperature
(°C)
A 2.65 ~ 2.85 81 ~ 91 2.77 ~ 2.97 78 ~ 88
B 2.55 ~ 2.75 54 ~ 64 2.67 ~ 2.87 53 ~ 63
C 0.63 ~ 0.69 10 ~ 15 0.57 ~ 0.62 9~14
D 0.58 ~ 0.64 9~14 0.55 ~ 0.60 8~13
Note: Indoor temperature at 29°C (DB), 19°C (WB) and Outdoor at
46°C (DB), 24°C (WB) for Cooling.
4.2.2. Heating.
CW-A180ES CW-A240ES
Item Pressure
(MPa)
Temperature
(°C)
Pressure
(MPa)
Temperature
(°C)
A 0.26 ~ 0.32 -9 ~ -1 0.26 ~ 0.32 -10 ~ -3
B 0.40 ~ 0.47 0~4 0.42 ~ 0.49 1.5 ~ 5.5
C 1.34 ~ 1.44 32 ~ 42 1.52 ~ 1.62 42 ~ 48
D 1.49 ~ 1.59 41 ~ 57 1.62 ~ 1.72 50 ~ 60
Note: Indoor temperature at 20°C (DB), 15.5°C (WB) and Outdoor at
7°C (DB), 6°C (WB) for Heating.
4 Refrigeration Cycle Diagram
4.1. CW-C180ES, CW-C240ES & CW-SC180ES.
4.2. CW-A180ES & CW-A240ES.