8.1.1. Electrical Work.
Always use at the rated voltage and with a specific air
conditioning circuit.
Power supply point shall be the place where there is ease
for the power disconnection in case of emergency.
Some installation locations may require installation of a
short-circuit breaker.
A 16 Ampere time delay fuse or circuit breaker is required.
Nominal cross sectional area of power supply wire must be
3 core x 1.0 mm2 or above.
The power supply must be from an independent circuit.
All electrical installation must be made in accordance with
local wiring and safety regulations wherever applicable.
There must be a double pole switch with minimum of 3mm
contact gap in the fixed installation circuit (Applicable for
models without power supply plug only).
8.1.2. Select the Best Location.
Install the unit at the nearest power outlet.
The air conditioner should be installed in a dry place where
there are no draughts.
Condensation from the air conditioner must be drained into
an appropriate location.
Do not install in a location where flammable gas leaks is a
possibility.
Usage in locations where the air is salty such as coastal
areas or near hot spas, or where sulphurous gas is
generated, may lead to a malfunction.
Do not install this appliance in a laundry room or other
locations where water may drip from the ceiling, etc.
Select an installation location which is rigid and strong
enough to support or hold the unit and select a location for
easy maintenance.
8 How to Install
8.1. Before installing air conditioner, please read the following:
8.2. Preparation for Installation.
There should not be any obstacles surrounding the unit.
Prepare an installation hole that is only slightly bigger than the cabinet size.
8
CW-C70YE / CW-C90YE