6 Wiring Diagram
6.1. Resistance of Fan Motor
windings and the rated
Capacitor
Model CW-XC100VK CW-XC120VK
Connection CWA951216 CWA951215
Blue - Yellow 34.6 Ω 34.8 Ω
Yellow - Brown 2.3 Ω 2.5 Ω
Brown - Orange 13.7 Ω 14.8 Ω
Red -Yellow 36.6 Ω 37.6 Ω
6.2. Resistance of Compressor
windings and the rated
Capacitor
Model CW-XC100VK CW-XC120VK
Connection CWB09623 CWB09624
C-R 0.690 Ω 0.724 Ω
C-S 2.429 Ω 2.168 Ω
Capacitor CWA312066 (40µF,
250VAC)
CWA312067 (45µ,
250VAC)
Note: Resistance at 20°C of Ambient Temperature.
7 Air Conditioner Performance Evaluation
Suction & Discharge Air
Temperature Difference
Current Determination Remedy
  •  8°C and over (14.4°F)   •  As specified.   •  Nothing wrong.   •  None.
  •  8°C and over (14.4°F)   •  Higher than specified.   •  Nothing wrong, outdoor
temperature is too high, heat
radiation is not efficient.
  •  Improve heat radiation.
  •  Under 8°C (14.4°F)   •  Higher than specified.   •  Something is preventing heat
radiation.
  •  Excessive amount of refrigerant.
  •  Improve heat radiation.
  •  Under 8°C (14.4°F)   •  Lower than specified.   •  Leakage of refrigerant or
refrigerant system is blocked.
  •  Locate and repair leak.
  •  Flush refrigeration cycle.
  •  Under 8°C (14.4°F)   •  Higher than specified by
50%.
  •  Compressor defect.   •  Replace the compressor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
7
CW-XC100VK / CW-XC120VK