What does it mean if my Panasonic OCU-CR200VF5 displays a refrigerant flood back alarm?
- LleblancshirleySep 8, 2025
If your Panasonic Heat Pump is showing a refrigerant flood back alarm, it indicates that the suction gas superheat of 1 K or below has continued for 2 minutes or longer. To resolve this, adjust the cooling unit (Evaporator) side to maintain suction gas superheat of 10 K or over, ensuring no frost remains in the cooling unit (Evaporator).