Calibration of the external temperature sensor (terminal Temp)
Is used to eliminate cable resistance for the temperature measuring and
thus correct the temperature reading from Temp if needed.
- 0 10 -100 100
55
Filter factor for temperature on analog input Temp
Low pass filter to avoid temperature spikes and flickering.
% 20 1 0 100
56
Calibration of the internal temperature sensor
Is used to correct the internal temperature reading if necessary.
- 0 10 -100 100
57
Display setting for Active mode
0 = Show the calculated setpoint
(SP
calc
)
1 = Show the room temperature
- 1 1 0 1
58
Display setting for the Setpoint mode
0 = Show the calculated setpoint (SP
calc
)
1 = Show the user defined setpoint adjustment (SP
adj
)
- 0 1 0 1
59 Intensity or "brightness" of display when in Active or Setpoint mode % 70 1 0 100
60 Intensity or "brightness" of display when in Idle mode % 25 1 0 100
61 The Modbus address the controller uses - 1 1 1 254
62
Modbus stop bits and parity
0 = 8N2 1 = 8O1 2 = 8E1 3 = 8N1
- 2 1 0 3
63
Timeout should be at least 1.5 times a character,
i.e. at least 2 ms (@9 600 baud)
ms 3 1 1 500
64
Answer delay should be at least 3.5 times a character,
i.e. at least 5 ms (@9 600 baud)
ms 5 1 1 500
65
0 = 4800 bps 1 = 9600 bps
2 = 19200 bps 3 = 38400 bps
- 1 1 0 3
11. Operation instructions of guide vane
Prior to operating the air conditioner, the guide vane should be adjusted with its opening angle among the yellow area at the right
side of the air supply outlet. After the air conditioner is turned off, please close the guide vane.
Notes:
1. Do not insert your fingers into the air supply outlet when manually adjusting the guide vane.
2. Condensate drops may be generated when the opening angle of the guide vane is too small.
3. Excessive noise may be generated when the opening angle of the guide vane is too large.