Variable address Description Unit
Default
value
Scale
Min
value
Max
value
11
Number of fan speed used
1 = 1 fan speed is used
2 = 2 fan speeds are used
3 = 3 fan speeds are used
- 3 1 1 3
12
Change-over mode (0-3) and fan release function (4-7) via heat pump
supply sensor
0 = Manual setting in display 1 = Manual Heat
2 = Manual Cool
3 = Automatic via analog or digital input
4 = manual setting in the display via button 5 = Manual Heat
6 = Manual Cool
7 = Automatic via digital input DI
- 4 1 0 7
13
Temperature difference between the room temperature and the water
temperature to switch to heating (P009 = 3) or to release the fan at heat
mode (P009 = 7)
K 30 10 10 250
14
Temperature difference between the room temperature and the water
temperature to switch to cooling (P009 = 3) or to release the fan at cool
mode (P009 = 7)
K 30 10 10 250
15 Switch on delay for terminal DI min 0 1 0 120
16 Switch off delay for terminal DI min 0 1 0 120
17
Remote setting of the current controller state 0 = Off
1 = No Action 2 = Standby 3 = No Action 4 = Occupied
5 = No remote control
- 5 1 0 5
18-29 Not used
30
Manual or Auto control of output for Heat valve (terminal Heat)
0 = Manual Off
1 = Manual On
2 = Auto (output is controlled by the heat demand)
- 2 1 0 2
31
Manual or Auto control of output for Cool valve (terminal Cool)
0 = Manual Off
1 = Manual On
2 = Auto (output is controlled by the cool demand)
- 2 1 0 2
32-33 Not used
34
Manual/Auto Fan control, 3-speed
fan 0 = No fan speed active
1 = Fan speed 1 is active on DO FAN1
2 = Fan speed 2 is active on DO FAN2
3 = Fan speed 3 is active on DO FAN3
4 = Auto. Fan speed follows heat or cool demand according to the
application.
- 4 1 0 4
35-36 Not used
37
User defined setpoint adjustment (SP
adj
) set by using the buttons on
the front. Can be reset remotely. 0 = No current setpoint adjustment
made.
K 0 10 -200 200
38
Positive user defined setpoint adjustment.
The maximum allowed setpoint adjustment (SP
adj
) increase.
K 30 10 0 200
39
Negative user defined setpoint adjustment.
The maximum allowed setpoint adjustment (SP
adj
) decrease.
K 30 10 0 200
40-43 Not used
44 Heat valve exercise hour, 0 – 23h h 23 1 0 23
45 Cool valve exercise hour, 0 – 23h h 23 1 0 23
46
Sensor connected to AI Temp
0 = No sensor connected (Internal room sensor is used) 1
= Room temperature sensor
2 = Change-over temperature sensor or fan release function
- 2 1 0 2
47 Not used
48
Contact/detector connected to the terminal DI
0 = No contact connected 1-2 = Not used
3 = Presence detector (activate Occupied state) 4
= Change-over contact
- 0 1 0 4
49-52 Not used
53
Display inactive delay
Delay for the display to dim down to Idle mode. If
set to 0 the display never dims down.
s 0 30 0 600