22
10.3 Coils Register
1
Minimum fan speed. The fan runs at least at speed 1, except in Off state.
0 = Not Active 1 = Active
2
Mould protection
0 = Not Active 1 = Active
10
0 = NO 1 = NC
15
NC/NO for terminal Heat
16
NC/NO for terminal Cool
0 = NO 1 = NC
10.4 Input Register
Regin Model number (= 1715)
4
0 = Beta status
8
Heating/cooling mode 0 = Not used
1 = Heating
2 = Cooling
9
Controller state
0 = Off
1 = Not used 2 = Standby 3 = Not used
4 = Occupied
10
Room temperature
The current room temp, from the internal or the external sensor.
11
Change-over temperature or fan release temperature
The current change-over temperature. Shows NaN! if no sensor is connected.
20
Room temperature (internal)
The value from the internal temperature sensor.
21
Room temperature (external)
The value from the external temperature sensor. Shows a value if a temperature sensor is
configured for Temp/AI, NaN! otherwise.
22
The value from the external change-over temperature sensor. Shows a value if a change-
over sensor is configured for Temp/AI, NaN! otherwise.
25
AI Temp Raw
Raw value of the terminal (before any filters). Shows NaN! if no sensor is connected.
27
AI Temp
Value of the Analog input after filters and scaling. Shows NaN! if no sensor is connected.
29
The setpoint for the controller (SP
calc
), calculated from the basic setpoint,
setpoint
adjustment and hysteresis.
10.5 Holding Register
Variable address Description Unit
Default
value
Scale
Min
value
Max
value
1
Basic setpoint (SP
basic
)
°C 200 10 50 500
2 Hysteresis to calculate Heating and Cooling setpoint at Occupied state °C 10 10 10 400
3 Hysteresis to calculate Heating and Cooling setpoint at Standby state K 50 10 10 400
4 DeltaT, temperature span for On/Off control K 10 10 5 100
5
Controller mode
0 = 2-pipe
1 = 4-pipe
- 0 1 0 1
6
0 = No fan control
1 = Fan is controlled by heat command 2 = Fan is controlled by cool demand
3 = Fan is controlled by both heat and cool demand
- 3 1 0 3