2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
Item code Item
Setting data
No. Description
(1B) Forced thermostat ON time
0000 5 minutes
0001 4 minutes
Cooling discharge
temperature shift
–010 –10°C
–009 –9°C
–008 –8°C
0010 10°C
Heating discharge
temperature shift
–010 –10°C
–009 –9°C
–008 –8°C
0010 10°C
Temperature shift for
cooling/heating change in
auto heat/cool mode
0001 ±1°C
0002 ±2°C
0003 ±3°C
0007 ±7°C
(Upper limit)
Change to remote
control temperature
setting range
Cooling
0018 18°C (Lower limit at shipment)
0019 19°C
(Lower limit)
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
Heating
0016 16°C (Lower limit at shipment)
0017 17°C
(Lower limit)
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
Drying
0018 18°C (Lower limit at shipment)
0019 19°C
(Lower limit)
0029 29°C
0030 30°C (Upper limit at shipment)
(Upper limit)
Auto heat/cool
0017 17°C (Lower limit at shipment)
0018 18°C
(Lower limit)
0026 26°C
0027 27°C (Upper limit at shipment)
Humidifi er operation
0000 Normal
0001 Ignore heat exchanger temperature conditions.
Filter (CN70) input
switching
0000 Filter input (differential pressure switch input)
0001 Alarm input (for trouble input about air cleaner or similar device)
0002
Humidifi er input (Operates linked with drain pump when humidifi er is
ON.)
Indoor unit electronic
control valve
0000 Present (Setting at shipment)
0002 None
T10 terminal switching
0000 Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001 Used for OFF reminder
0002 Fire prevention input