EasyManua.ls Logo

Panasonic S-15MF3E5AN - Specifications; Indoor unit

Panasonic S-15MF3E5AN
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Operation condition temperature range
•Coolingmode:14°C~25°CWB
•Heatingmode:16°C~30°CDB
* In the case of nanoe™ X ‘‘OFF’
** Fan speed display on the remote controller
High :
(CZ-RTC4), (CZ-RTC5B, CZ-RTC6 series)
Medium :
(CZ-RTC4), (CZ-RTC5B, CZ-RTC6 series)
Low :
(CZ-RTC4), (CZ-RTC5B, CZ-RTC6 series)
Middle Static Pressure Duct
Model Name S-60MF3E5AN S-73MF3E5AN S-90MF3E5AN
Power source 220 - 230 - 240 V
50 - 60 Hz
Cooling capacity
kW
6.0 7.3 9.0
BTU/h
20,500 24,900 30,700
Sensible
kW
4.6 5.3 6.6
Latent kW
1.4 2.0 2.4
Heating capacity
kW
7.1 8.0 10.0
BTU/h
24,200 27,300 34,100
Cooling electric
power input*
kW
0.079 0.079 0.136
Heating electric
power input*
kW
0.079 0.079 0.136
Sound
pressure
level **
High dB(A)
31 31 35
Medium dB(A)
28 28 33
Low dB(A)
23 23 25
Sound
power
level **
High dB(A)
54 54 58
Medium dB(A)
51 51 56
Low dB(A)
46 46 48
Unit dimensions
(H×W×D)
mm
250×1,000×730 250×1,000×730 250×1,000×730
Net weight
kg
31 31 31
Specications
Indoor unitIndoor unit
01_350312_EN.indb 13 2023/3/17 9:53:35