1-1-1-1-6
11
Single-Type
1-1. Unit Specications
PZH2
High Static Pressure Ducted Type S-224PE3R5B / U-224PZH2R8
INDOOR MODEL S-224PE3R5B - -
PANEL MODEL - - -
OUTDOOR MODEL - U-224PZH2R8 -
Branch pipe MODEL -
Performance test condition ISO13253 / AS / NZS3823.1
Power supply
ø, Hz 1ø 50Hz 3Ø 50Hz -
V - 230V 240V - 400V 415V Min Max
C
O
O
L
I
N
G
Capacity
kW - 22.4 22.4 - - - 5.7 25.0
BTU/h - 76400 76400 - - - 19400 85300
Current A - 4.20 4.10 - 9.95 9.60 - -
Input power
W - 830 830 - 6.410k 6.410k - -
TOTAL W - - 7.240k 7.240k 1.500k 9.200k
Annual consumption
TOTAL kWh *4 - - - - 3620 - - -
EER/AEER/STR RAT
TOTAL (W/W) - - - - 3.09/3.04/- 3.09 3.80 2.72
Power factor % - - - - 93 93 - -
Noise indoor
dB-A (H/M/L) 47/45/42 - - -
Power Level dB 79/77/74 - - -
Noise outdoor
dB-A (H/L) - 58/- - -
Power Level dB - 77/- - -
H
E
A
T
I
N
G
Capacity
kW - 25.0 25.0 - - - 4.9 28.0
BTU/h - 85300 85300 - - - 16700 95500
Current A - 4.20 4.10 - 9.75 9.40 - -
Input power
W - 830 830 - 6.270k 6.270k - -
TOTAL W - - 7.100k 7.100k 1.010k 8.700k
COP/ACOP/STR RAT TOTAL (W/W)*5 / ("A"~"G")
- - - - 3.52/3.46/- 3.52 4.85 3.22
Power factor % - - - - 93 93 - -
Noise indoor
dB-A (H/M/L) 47/45/42 - - -
Power Level dB 79/77/74 - - -
Noise outdoor
dB-A (H/L) - 62/- - -
Power Level dB - 81/- - -
EXTRA LOW TEMP
Total capacity(kW)/Input power(W)/COP
- -
Max Current(A) / Max Input power(W) - 6.40/1440 6.30/1440 - 16.5/10.6k 16.5/11.0k -
Starting current(A) (Cooling/Heating) - - - - 9.95/9.75 9.60/9.40 -
Comp output(W) - - 5.50k 5.50k -
Time Delay fuse max size(A) 15 30 -
Network Impedance (Ω MAX.) - - -
Fan motor output (Indoor/Outdoor) W 750 × 2 120 × 2 -
Moisture removal volume L/h(Pt/h) 6.2 (6.2×1) (13.0) - -
External static pressure Pa 75 / (130/200) - -
Indoor
Air ow
Cooling m
3
/min (m
3
/h) (H/M/L) 84.0/72.0/59.0 (5040)/(4320)/(3540) - - -
Heating m
3
/min (m
3
/h) (H/M/L) 84.0/72.0/59.0 (5040)/(4320)/(3540) - - -
Outdoor
Air ow
Cooling m
3
/min (m
3
/h) - 160 (9600) - -
Heating m
3
/min (m
3
/h) - 160 (9600) - -
Refrigerant type / amount
g
(oz) - R32 5.20k (183.4) - -
Product dimension
Height mm (inch) 486 (19-1/8) 1500 (59-1/16) -
Width mm (inch) 1456 (57-5/16) 980 (38-37/64) -
Depth mm (inch) 916 (36-1/16) 370 (14-9/16) -
Product dimension (Panel)
H×W×D mm, inch - - - -
Packing dimension
Height mm (inch) 610 (24-1/32) 1642 (64-41/64) -
Width mm (inch) 1646 (60-13/16) 1095 (43-7/64) -
Depth mm (inch) 1132 (44-9/16) 529 (20-53/64) -
Weight
(NET) k
g
(lb) 88 (195) 128 (282) -
(GROSS) k
g
(lb) 108 (239) 140
(309) -
Panel (NET)
k
g
(lb) - - - -
Layers limit (actually) 4 (5) 1(2) -
Operation condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
Max Working Pressure HP/LP Mpa (bar) 4.15/2.70(41.5/27.0) -
P
I
P
I
N
G
Pipe port diameter mm (inch) (Liquid)Ø12.7(1/2) (Gas)Ø19.05(3/4) (Liquid)Ø12.7(1/2) (Gas)Ø19.05(3/4) -
Pipe diameter mm (inch)
(Under 30m)
(Liquid)Ø12.7(1/2) (Gas)Ø19.05(3/4) -
Pipe diameter mm (inch)
(Over 30m)
(Liquid)Ø12.7(1/2) (Gas)Ø25.4(1)
Standard length m(ft)
7.5 (24.6)
-
Connecting method,
(Under 30m)
(Liquid)ared type (Gas)brazing connection
(Liquid)&(Gas) ared type -
(Over 30m)
(Liquid)ared type (Gas)brazing connection
Pipe length range m (ft) 5 ~ 60m (16.4 ~ 196.9) -
Indoor unit & Outdoor unit height difference m (ft)
30m (OD located lower) / 30m (OD located higher) (98.4/98.4) -
Add gas amount
g
/m (oz/ft)
(Under 30m)
- -
Add gas amount
g
/m (oz/ft)
(Over 30m)
80
g
/m (0.860)
Pipe length for additional gas m (ft) 30m (98.4) -
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.