11
4. Installing the Drain Pipe
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for the drain
and use the supplied hose band to prevent water leaks.
The PVC pipe must be purchased separately.
The transparent drain part on the unit allows you to check
drainage.
CAUTION
no trop noitcennoc niard eht ta epat evisehda esu ton oD
the indoor unit.
neht dna ,tekcos eht stcatnoc ti litnu epip niard eht tresnI
secure it tightly with the hose band.
ti peek esaelp ,esoh niard deilppus eht dneb ton oD
straight.
ecaf stun gnikcol rieht os spmalc esoh eht nethgiT
upward. (Fig. 1-11-2-1-9)
Hose band (Supplied)
Drain insulator (Field supply)
(The thickness must be at
least 8 mm.)
Drain hose with
heat insulator
(Supplied)
PVC pipe
(O.D. ø32)
(Field supply)
To be glued
Please do not glue.
Make sure that there is no clearance here.
Fig.1-11-2-1-9
(2) After connecting the drain pipe securely, wrap the supplied
packing and drain pipe insulator around the pipe, then secure
it with the vinyl clamps . (Fig. 1-11-2-1-10)
Drain insulator (Field supply)
Vinyl clamps
(Field supply)
Fig.1-11-2-1-10
NOTE
Make sure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
CAUTION
ot retaw esuac yam siht sa redeelb ria na llatsni ton oD
spray from the drain pipe outlet. (Fig. 1-11-2-1-11)
Prohibited
Air bleeder
Fig.1-11-2-1-11
Drainage hole
Foam drain socket
(Supplied)
Hose band
(Supplied)
Fig.1-11-2-1-12
eht morf tneidarg drawpu na htiw epip eht llatsni ton oD
connection port. This will cause the drain water to ow
backward and leak.
(Fig. 1-11-2-1-13)
Prohibited
Upward gradient
Fig.1-11-2-1-13
nehw edis tinu eht no gnipip eht ot ecrof ylppa ton oD
connecting the drain pipe. The pipe should not be allowed to
hang unsupported from its connection to the unit. Fasten the
pipe to a wall, frame, or other support as close to the unit as
possible. (Fig. 1-11-2-1-14)
Support pieces
1.5m~2m
(0.5m)
Fig.1-11-2-1-14
foor eht ot detroppus era sepip CVP gnitcennoc lla erus ekaM
structure, and the drain line is installed straight.
5. Connecting Duct to Indoor Unit
(1) Install the duct (Field supply) for the Dimension of the
installation hole.
Use M5 self-tapp Screws for installation.
(2) The duct connection of the air outlet needs thermal insulation.
Thermal insulator
(Local arrangement)
Air outlet
Fig.1-11-2-1-15
NOTE
Select an air-intake grille with a filter at a local shop.
eht fo efil ecivres eht dnetxe ot dna ria naelc teg oT
air conditioner, an air filter must be installed in the air
intake. For installation and cleaning the air filter, consult
your dealer or service center.