5 - 6
1. Simple Settings Function
5
VRF SYSTEMS Indoor Unit
Simple setting items
Item code Item Description
01
Filter sign ON time setting
(filter lifetime)
Changes the indoor unit filter lifetime when a high-performance filter or other
optional product is installed.
02 Degree of filter fouling
Reduces the filter sign ON time to 1/2 of the standard time (setting at the time of
shipping) for cases when filter fouling is more severe than normal.
Filter sign ON times for each model
Model
data
Model
Filter sign ON time
Standard Long-life
Standard High fouling Standard High fouling
0001
4-Way cassette (U1, U2)
4-Way cassette 60 × 60 (Y2)
× × 2500 1250
0005
Low Silhouette Ducted (F2)
Slim Low Static Ducted (M1)
× × × ×
0006
High Static Pressure
Ducted (E2)
× × × ×
0007 Ceiling (T2) × × 1500 750
0008 Wall Mounted (K1, K2) 150 75 × ×
Unit: hour
NOTE
•
×
indicates that there is no corresponding filter.
•
150
indicates the filter sign ON time that is set at shipment.
• High fouling: Set when
is selected for the degree of filter fouling (item code ).
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 6 17/03/08 18:33:42