24
4-Way Cassette (2-way airflow)
Use or nonuse of R32
refrigerant leakage
detection sensor
Nonuse Use
Capacity of indoor unit
22~160 ~36 45 56 60 73, 90 106~
Refrigerant charge amount (kg)
Floor area of the room (m
2
)
82 11.3 11.3 11.3 11.3 11.3 11.3 11.3
84 11.5 11.5 11.5 11.5 11.5 11.5 11.5
86 11.6 11.6 11.6 11.6 11.6 11.6 11.6
88 11.7 11.7 11.7 11.7 11.7 11.7 11.7
90 11.9 11.9 11.9 11.9 11.9 11.9 11.9
92 12.0 12.0 12.0 12.0 12.0 12.0 12.0
94 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0) 12.1 (12.0)
96 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0) 12.3 (12.0)
98 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0) 12.4 (12.0)
100 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0) 12.5 (12.0)
( ) : U-4LZ2E5, U-5LZ2E5, U-6LZ2E5, U-4LZ2E8, U-5LZ2E8, U-6LZ2E8
01_350115_EU_Eng.indb 24 2023/3/1 13:52:45