ii
i
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and 
operating standards. As the installer or service person, 
it is an important part of your job to install or service the 
system so it operates safely and efficiently.
For safe installation and trouble-free operation, you 
must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
This product is intended for professional use.
Permission from the power supplier is required when 
installing the U-8ME1E81 outdoor unit that is connected 
to a 16 A distribution network.
This equipment complies with EN/IEC 61000-3-12 
provided that the short-circuit power Ssc is greater than 
or equals to the values corresponding to each model as 
shown in the table below at the interface point between 
the user’s supply and the public system.
It is the responsibility of the installer or user of the 
equipment to ensure; by consultation with the distribution 
network operator if necessary that the equipment is 
connected only to supply with a short-circuit power Ssc 
greater than or equals to the values corresponding to 
each model as shown in the table below.
U-10ME1E81U-12ME1E81U-14ME1E81U-16ME1E81U-18ME1E81U-20ME1E81
U-10ME1E81U-12ME1E81U-14ME1E81U-16ME1E81U-18ME1E81U-20ME1E81
Ssc
1,150 kVA1,550 kVA 1,550 kVA1,550 kVA 1,550 kVA 1,550 kVA
This equipment complies with EN/IEC 61000-3-11 
provided that the system impedance Zmax is less than 
or equal to the values corresponding to each model as 
shown in the table below at the interface point between 
the user’s supply and the public system. Consult with 
the supply authority for the system impedance Zmax.
Zmax
— 0.290 0.290  0.290 
0.290  0.290 
Pay close attention to all warning and caution notices 
given in this manual.
WARNING
This symbol refers to a hazard or unsafe 
practice which can result in severe 
personal injury or death.
CAUTION
This symbol refers to a hazard or 
unsafe practice which can result in 
personal injury or product or property 
damage.
If Necessary, Get Help
These instructions are all you need for most installation 
sites and maintenance conditions. If you require help for a 
special problem, contact our sales/service outlet or your 
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for 
improper installation or maintenance service, including 
failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
WARNING
When Wiring
ELECTRICAL SHOCK CAN 
CAUSE SEVERE PERSONAL 
INJURY OR DEATH. 
ONLY A QUALIFIED, 
EXPERIENCED ELECTRICIAN 
SHOULD ATTEMPT TO WIRE 
THIS SYSTEM.
• Do not supply power to the unit until all 
wiring and tubing are completed or 
reconnected and checked.
• Highly dangerous electrical voltages are 
used in this system. Carefully refer to 
the wiring diagram and these instructions 
when wiring. Improper connections and 
inadequate grounding can cause 
accidental injury or death. 
• Connect all wiring tightly. Loose wiring 
may cause overheating at connection 
points and a possible fire hazard.
• Provide a power outlet to be used 
exclusively for each unit.
• ELCB must be incorporated in the fixed 
wiring.Circuit breaker must be 
incorporated in the fixed wiring in 
accordance with the wiring regulations.
U-8ME1E81 U-10ME1E81 U-12ME1E81 U-14ME1E81
Circuit
breaker
25 A 25 A 35 A 35 A
U-16ME1E81U-18ME1E81U-20ME1E81
Circuit
breaker
45 A 50 A 50 A
• Provide a power outlet exclusively for 
each unit, and full disconnection means 
having a contact separation in all poles 
must be incorporated in the fixed wiring 
in accordance with the wiring rules.
• To prevent possible hazards from 
insulation failure, the unit must be 
grounded.
…In an Area with High Winds
Securely anchor the outdoor unit down 
with bolts and a metal frame. Provide a 
suitable air baffle.
…In a Snowy Area 
(for Heat Pump-type Systems)
Install the outdoor unit on a raised 
platform that is higher than drifting snow. 
Provide snow vents.
When Connecting Refrigerant Tubing
WARNING
• When performing piping work do 
not mix air except for specified 
refrigerant (R410A) in refrigeration
 
cycle. It causes capacity down, 
and risk of explosion and injury 
due to high tension inside the 
refrigerant cycle.
•
•
Refrigerant gas leakage may 
cause fire.
Do not add or replace refrigerant 
other than specified type. It may 
cause product damage, burst and 
injury, etc.
•
•
•
• Apply refrigerant lubricant to the 
matching surfaces of the flare and 
union tubes before connecting them, 
then tighten the nut with a torque 
wrench for a leak-free connection.
•
•
Ventilate the room well, in the event 
that is refrigerant gas leaks during the 
installation. Be careful not to allow 
contact of the refrigerant gas with a 
flame as this will cause the generation 
of poisonous gas.
Keep all tubing runs as short as 
possible.
Use the flare method for connecting 
tubing.
Check carefully for leaks before 
starting the test run.
Do not leak refrigerant while piping 
work for an installation or 
re-installation, and while repairing 
refrigeration parts. 
Handle liquid refrigerant carefully as it 
may cause frostbite.
When Transporting
Be careful when picking up and moving 
the indoor and outdoor units. Get a 
partner to help, and bend your knees 
when lifting to reduce strain on your back. 
Sharp edges or thin aluminum fins on the 
air conditioner can cut your fingers.
When Installing…
Select an installation location which is 
rigid and strong enough to support or 
hold the unit, and select a location for 
easy maintenance.
…In a Room
Properly insulate any tubing run inside a 
room to prevent “sweating” that can 
cause dripping and water damage to 
walls and floors.
CAUTION
Keep the fire alarm and the air 
outlet at least 1.5 m away from the 
unit.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete 
blocks to provide a solid, level foundation 
for the outdoor unit. This prevents water 
damage and abnormal vibration.
SM830204-05_2WAY SYS_new.indb   3 15/01/05   11:56:43