EasyManua.ls Logo

Panasonic S-36PF1U6 - Misoperation Alarm Indicators

Panasonic S-36PF1U6
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
5-11. Misoperation Alarm Indicators
Alarm indicator lamps on the indoor unit indicate the error
cause if the air conditioner fails to operate upon being
switched on. The possible alarm indications are given in
Table 5-1. Fig. 5-12 shows the location of the alarm lamps
on the indoor unit.
(See Table 5-1 and Fig. 5-12.)
Table 5-1
Alarm
(OPERATION
(TIMER
(STANDBY
Cause of Trouble
lamp) lamp) lamp)
S.C. errors* between the indoor unit’s controller (PCB) and the remote
controller.
Compressor protector is working.
S.C. errors between indoor and outdoor units.
Indoor or outdoor thermistor is malfunctioning.
Outdoor unit protector is working.
Indoor unit protector is working.
TEST RUN switch on the operation controller is in ON state.
* S.C.: Serial communications
OPERATION
lamp
TIMER
lamp
STANDBY
lamp
Remote control
receiver
Fig. 5-12
NOTE
Stick the alarm message label accompanying the
wireless remote controller on the electrical component
box to indicate the cause of trouble for future reference.
PanasonicPAC-iIndoorUnitUS-le4545PanasonicPAC-iIndoorUnitUS-le4545 2011/11/0215:17:352011/11/0215:17:35

Table of Contents

Other manuals for Panasonic S-36PF1U6

Related product manuals