EasyManua.ls Logo

Panasonic S-36PN1E5

Panasonic S-36PN1E5
739 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
1-437
7-8. External Static Pressure Setting for AC Fan Motor Model
To apply to following models
S-36PN1E5 , S-45PN1E5 , S-50PN1E5
There are two tap connector located in indoor unit control box can be selected.
The “blue connector” is standard tap, use-as-is at shipment.
For high static pressure duct, switch Fan Motor connector to plug in
boost tap “white connector” to elevate air volume.
0
10
20
30
40
50
60
70
80
188
0
10
20
30
40
50
60
70
80
2010
P-Q CURVE
External Static Pressure (Pa)
Air Volume (m
3
/min.)
Lo
S-36PN1E5
P-Q CURVES-45PN1E5, S-50PN1E5
Me
standard tap Hi
boost tap SHi
Lo
Me
standard tap Hi
boost tap SHi
External Static Pressure (Pa)
Air Volume (m
3
/min.)
SM830211-07PAC-i.indb437SM830211-07PAC-i.indb437 2013/09/1722:48:382013/09/1722:48:38