1
1-298
Case 1
Automatic address setting from the outdoor unit (K1 type)
If the power can be turned ON separately for the indoor and outdoor units in each system:
The indoor unit addresses can be set without running the compressor.
Be sure to use a jig for short-circuiting.
System address
No.
System address
10s digit
(2P DIP switch)
System address
1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = “0”)
Both OFF
ON
12
ON
OFF
1 (If outdoor unit is No. 1)
Both OFF
ON
12
ON
OFF
2 (If outdoor unit is No. 2)
Both OFF
ON
12
ON
OFF
11 (If outdoor unit is No. 11)
10s digit ON
ON
12
ON
OFF
21 (If outdoor unit is No. 21)
20s digit ON
ON
12
ON
OFF
30 (If outdoor unit is No. 30)
10s digit and 20s
digit ON
ON
OFF
ON
12
“0” setting
“1” setting
“2” setting
“1” setting
“1” setting
“0” setting
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Short-circuit the AUTO ADD (CN041) pin.
The compressor operates when the power is turned ON at a different outdoor unit.
(2) Next, turn ON the power only at the indoor and outdoor units in a different system.
Short-circuit the AUTO ADD (CN041) pin.
(3) Operation using the remote controller is now possible.
Communication for automatic address setting begins.
<Approximately 4 – 5 minutes are required.>
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
SM830231-00Single欧州.indb298SM830231-00Single欧州.indb298 2014/06/0510:12:372014/06/0510:12:37