1-190
1
Simultaneous (Twin) -Type
1-1. Unit Specifi cations
PEY1
5. Ducted Type S-36PN1E5A×2 / U-71PEY1E5
INDOOR MODEL S-36PN1E5A×2
PANEL MODEL -
OUTDOOR MODEL U-71PEY1E5
Branch pipe MODEL -
PERFORMANCE TEST CONDITION ISO13253 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz 1ø 50Hz 1ø 50Hz
V 220 230 240 220 230 240 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 7.1 7.1 7.1 2.0 7.7
BTU/h 24200 24200 24200 6800 26300
CURRENT A 0.42×2 0.43×2 0.44×2 12.0 11.5 11.0 - -
INPUT POWER
W 90×2 95×2 100×2 2.430k 2.432k 2.434k - -
TOTAL W - 2.610k 2.620k 2.630k 325 3.300k
ANNUAL CONSUMPTION
TOTAL kWh
*
4 - - 1310 - - -
EER/EER CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 2.72 2.71 / D 2.70 6.15 2.33
Erp
*
6
Pdsign kW - - - - 7.1 -
SEER (W/W) - - - - 5.0 -
Annual consumption
kWh - - - - 496 -
Class - - - - B -
POWER FACTOR % - - - 92 92 92 - -
NOISE INDOOR
(H/M/L)
dB-A 40/38/35 -
Power Level dB 57/55/52 -
NOISE OUTDOOR
(H/L)
dB-A 50/-
Power Level dB 70/-
H
E
A
T
I
N
G
CAPACITY
kW 7.1 7.1 7.1 1.8 8.1
BTU/h 24200 24200 24200 6100 27600
CURRENT A 0.42×2 0.43×2 0.44×2 9.60 9.20 8.90 - -
INPUT POWER
W 90×2 94×2 98×2 1.940k 1.940k 1.940k - -
TOTAL W - 2.120k 2.130k 2.140k 275 2.840k
COP/COP CLASS
TOTAL(W/W)
*
5/("A"~"G")
- - - 3.35 3.33 / C 3.32 6.55 2.85
Erp
*
6
Pdsign kW - - - - 5.1 -
Tbivalen °C - - - - -7 -
SCOP (W/W) - - - - 3.8 -
Annual consumption
kWh - - - - 1877 -
Class - - - - A -
POWER FACTOR % - - - 92 92 91 - -
NOISE INDOOR
(H/M/L)
dB-A 40/38/35 - ⁄ ⁄
Power Level dB 57/55/52 -
NOISE OUTDOOR
(H/L)
dB-A - 52/- ⁄ ⁄
Power Level dB - 70/-
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.60×2/130×2 0.62×2/140×2 0.63×2/150×2 18.0/3.640k 18.0/3.810k 18.0/3.970k ⁄
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 11.8/2.5k 11.3/2.5k 10.8/2.5k⁄
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 60×2 90 ⁄
MOISTURE REMOVAL VOLUME L/h(Pt/h) 4.2 (2.1×2) (8.8) -
External static pressure
Pa
50 (MIN10 - MAX80)
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) [14/12/10 (494/424/353)]×2
HEAT m
3
/min (ft
3
/min) [14/12/10 (494/424/353)]×2
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 39 (1377)
HEAT m
3
/min (ft
3
/min) 39 (1377)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 1.70k (60.0) /
P
R
O
D
I
M
HEIGHT : H mm(inch) 250 (9-27/32) 569 (22-13/32) /
WIDTH : W mm(inch) 780 (+100) (30-23/32) (+3-15/16) 790 (31-7/64) /
DEPTH : D mm(inch) 650 (25-19/32) 285 (11-7/32) /
P
A
C
D
I
M
HEIGHT : H mm 345 645 /
WIDTH : W mm 1007 921 /
DEPTH : D mm 777 386 /
MASS
(NET) k
g
(lb) 29 (64) 42 (93) /
(GROSS) k
g
(lb) 34 (75) 46 (101) /
LAYERS LIMIT (actually) 8 (9) 4 (5)
Operation
Condition
Cool O.D(DBT) 18°C ~ 32°C -10°C ~ 43°C
Heat O.D(DBT) 16°C ~ 30°C -15°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50 (16.4 ~ 164.0) ~ ~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
40 (0.430)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
20 (65.6)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.