3-6. Important Note for Wiring 4-Way Cassette 60 × 60 Type
(1)  The power supply inlet is located at the lower 
area of the refrigerant tubing side. 
The electrical component box is located at the  
refrigerant tubing side.
(2)  Before installing the panel for cassette, be sure 
to carry out the wiring connection.
(3)  Remove the lid located on the electrical 
component box by unscrewing the screws 
(M4 × L6) (×4).
(4)  Lead the wires from the power supply inlet to 
the unit. Be sure to lead the wires through the 
power supply inlet. Make sure that no wire is 
caught between the indoor unit and panel for 
cassette. Otherwise, the unit may cause a fire.
(5)  Connect the wires into the terminals through 
the power supply inlet for the electrical 
component box. 
Fix the wires with a clamping clip.
(6)  Reinstall the lid of the electrical component box in its original position with paying attention 
not to have the wires caught in the lid. 
See Section “4. ELECTRICAL WIRING”.
< When connecting to optional parts >
●
   Connecting to Schedule Timer or Seri-Para I/O Unit 
Connect the wire from Schedule Timer or Seri-Para I/O Unit to the indoor unit control PCB 
T10 (CN061, Yellow) and functional ground screw.
Power supply inlet
Screws (M4 × L6) position
Functional 
ground screw
Power wiring (T10)
Service entrance
Clamper (supplied):
Wind the drain pump wiring and ferrite core by the 
clamper and band them together to avoid noise caused 
by vibration as a result of the ferrite core riding on the 
metal plate. 
Metal plate
T10
Ferrite Core
Drain pump wiring
Clamper
(supplied)