3-6. Important Note for Wiring 4-Way Cassette 60 × 60 Type
(1) The power supply inlet is located at the lower
area of the refrigerant tubing side.
The electrical component box is located at the
refrigerant tubing side.
(2) Before installing the panel for cassette, be sure
to carry out the wiring connection.
(3) Remove the lid located on the electrical
component box by unscrewing the screws
(M4 × L6) (×4).
(4) Lead the wires from the power supply inlet to
the unit. Be sure to lead the wires through the
power supply inlet. Make sure that no wire is
caught between the indoor unit and panel for
cassette. Otherwise, the unit may cause a fire.
(5) Connect the wires into the terminals through
the power supply inlet for the electrical
component box.
Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its original position with paying attention
not to have the wires caught in the lid.
See Section “4. ELECTRICAL WIRING”.
< When connecting to optional parts >
Connecting to Schedule Timer or Seri-Para I/O Unit
Connect the wire from Schedule Timer or Seri-Para I/O Unit to the indoor unit control PCB
T10 (CN061, Yellow) and functional ground screw.
Power supply inlet
Screws (M4 × L6) position
Functional
ground screw
Power wiring (T10)
Service entrance
Clamper (supplied):
Wind the drain pump wiring and ferrite core by the
clamper and band them together to avoid noise caused
by vibration as a result of the ferrite core riding on the
metal plate.
Metal plate
T10
Ferrite Core
Drain pump wiring
Clamper
(supplied)