1-160
1
Simultaneous (Twin) -Type
1-1. Unit Specifi cations
PEY1
3. Wall Mounted Type S-50PK1E5A×2 / U-100PEY1E8
INDOOR MODEL S-50PK1E5A×2
PANEL MODEL -
OUTDOOR MODEL U-100PEY1E8
Branch pipe MODEL CZ-P155BK1
PERFORMANCE TEST CONDITION ISO5151 / EN14511 / EN14825 / EN12102
POWER SUPPLY
ø, Hz 1ø 50Hz 3ø 50Hz
V 220 230 240 380 400 415 Min Max
C
O
O
L
I
N
G
CAPACITY
kW 10.0 10.0 10.0 2.7 11.0
BTU/h 34100 34100 34100 9200 37500
CURRENT A 0.27×2 0.27×2 0.27×2 5.75 5.45 5.25 - -
INPUT POWER
W 26×2 27×2 28×2 3.515k 3.515k 3.510k - -
TOTAL W - 3.570k 3.570k 3.570k 530 4.200k
ANNUAL CONSUMPTION
TOTAL kWh 4 - - 1785 - - -
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
- - - 2.80 2.80 / C 2.80 5.09 2.62
Erp
6
Pdsign kW - - - - 10.0 -
SEER (W/W) - - - - 5.9 -
Annual consumption
kWh - - - - 593 -
Class - - - - A+ -
POWER FACTOR % - - - 93 93 93 - -
NOISE INDOOR
(H/M/L)
dB-A 40/36/32 -
Power Level dB 57/51/46 -
NOISE OUTDOOR
(H/L)
dB-A 54/-
Power Level dB 70/-
H
E
A
T
I
N
G
CAPACITY
kW 10.0 10.0 10.0 2.1 12.4
BTU/h 34100 34100 34100 7200 42300
CURRENT A 0.27×2 0.27×2 0.27×2 4.45 4.20 4.05 - -
INPUT POWER
W 26×2 27×2 28×2 2.720k 2.720k 2.715k - -
TOTAL W - 2.775k 2.775k 2.775k 410 4.000k
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
- - - 3.60 3.60 / A 3.60 5.12 3.10
Erp
6
Pdsign kW - - - - 10.0 -
Tbivalen °C - - - - -7 -
SCOP (W/W) - - - - 3.8 -
Annual consumption
kWh - - - - 3684 -
Class - - - - A -
POWER FACTOR % - - - 93 93 93 - -
NOISE INDOOR
(H/M/L)
dB-A 40/36/32 - ⁄ ⁄
Power Level dB 57/51/46 -
NOISE OUTDOOR
(H/L)
dB-A - 54/- ⁄ ⁄
Power Level dB - 70/-
EXTRA LOW TEMP
Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W) 0.27×2/26×2 0.27×2/27×2 0.27×2/28×2 9.0/5.550k 9.0/5.800k 9.0/6.050k ⁄
STARTING CURRENT(A)/COMP OUTPUT(W) - - - 5.75/1.7k 5.45/1.7k 5.25/1.7k⁄
NETWORK IMPEDANCE (ΩMAX.) - -
FM OUTPUT (W) 47×2 90 ⁄
MOISTURE REMOVAL VOLUME L/h(Pt/h) 6.0 (3.0×2) (12.6) -
External static pressure
Pa
-
I/D AIR
FLOW
COOL m
3
/min (ft
3
/min) [14/12/10.5 (494/424/371)]×2
HEAT m
3
/min (ft
3
/min) [14/12/10.5 (494/424/371)]×2
O/D AIR
FLOW
COOL m
3
/min (ft
3
/min) 76 (2684)
HEAT m
3
/min (ft
3
/min) 67 (2366)
REFRIGERANT TYPE, AMOUNT
g
(oz) R410A 2.60k (91.7) /
P
R
O
D
I
M
HEIGHT : H mm(inch) 300 (11-1/32) 996 (39-7/32) /
WIDTH : W mm(inch) 1065 (41-23/64) 940 (37-1/32) /
DEPTH : D mm(inch) 230 (9-1/32) 340 (13-13/32) /
P
A
C
D
I
M
HEIGHT : H mm 310 1136 /
WIDTH : W mm 1140 1055 /
DEPTH : D mm 380 485 /
MASS
(NET) k
g
(lb) 13 (29) 73 (161) /
(GROSS) k
g
(lb) 17 (37) 81 (179) /
LAYERS LIMIT (actually) 15 (16) 2 (3)
Operation
Condition
Cool O.D(DBT) 18°C ~ 32°C -10°C ~ 43°C
Heat O.D(DBT) 16°C ~ 30°C -15°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2) (Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl ared type, 5.0(16.4) fl ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50 (16.4 ~ 164.0) ~ ~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher) (49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50 (0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30 (98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830231-00Single欧州.indb160SM830231-00Single欧州.indb160 2014/06/0510:12:092014/06/0510:12:09