EasyManua.ls Logo

Panasonic S-71PU1E5A - Page 562

Panasonic S-71PU1E5A
659 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-40
5
H05 Sensor Failure, Compressor Discharge Temperature Sensor (TD) Disconnected
Error Detection Method
(In case of outdoor temperature over 5°C) For 10 minutes since started, variation of discharge temperature is always
detected within 2°C comparing with the temperature just before starting.
1.
(In case of outdoor temperature less than 5°C) For 30 minutes since started, variation of discharge temperature is
always detected within 2°C comparing with the temperature just before starting.
1-1
1-2
Reinstall correctly.
Yes
No
1
Sensor
Trouble
Replace the sensor with a new one.
1-2
Is the sensor properly installed at the holder side?
SM830231-00Single欧州.indb40SM830231-00Single欧州.indb40 2014/04/0217:47:292014/04/0217:47:29

Table of Contents

Other manuals for Panasonic S-71PU1E5A

Related product manuals