83
Specications
Low Silhouette Ducted
(Type F1)
Model Name
S-36PF1E5B S-45PF1E5B S-50PF1E5B S-60PF1E5B S-71PF1E5B
S-100P
F1
E5B S-125P
F1
E5B S-140P
F1
E5B
Power source (Europe) 220 - 230 - 240 V
50 Hz
Power source (Oceania) 230 - 240 V
50 Hz
Cooling capacity
kW
3.6 4.5 5.0 6.0 7.1 10.0 12.5 14.0
BTU/h
12,300 15,400 17,100 20,500 24,200 34,100 42,700 47,800
Sensible
kW
3.1 3.5 4.0 4.9 5.4 8.2 9.4 10.1
Latent
kW
0.5 1.0 1.0 1.1 1.7 1.8 3.1 3.9
Heating capacity
kW
4.2 5.2 5.6 7.0 8.0 11.2 14.0 16.0
BTU/h
14,300 17,700 19,100 23,900 27,300 38,200 47,800 54,600
Cooling electric
power input
kW
0.070 0.070 0.100 0.120 0.120 0.195 0.215 0.225
Heating electric
power input
kW
0.070 0.070 0.100 0.120 0.120 0.200 0.210 0.225
Sound
pressure
level
High dB(A)
33 34 34 35 35 38 39 40
Medium dB(A)
29 30 30 32 32 34 35 36
Low dB(A)
25 26 26 26 26 31 32 33
Sound
power
level
High dB(A)
55 56 56 57 57 60 61 62
Medium dB(A)
51 52 52 54 54 56 57 58
Low dB(A)
47 48 48 48 48 53 54 55
Unit dimensions
(H×W×D)
mm
290×800×700 290×800×700 290×800×700 290×1,000×700 290×1,000×700
290×1,400×700
290×1,400×700 290×1,400×700
Net weight
kg
28 28 28 33 33 45 45 45
Operation condition temperature range
•Coolingmode:14°C~25°CWB/18°C~32°CDB•Heatingmode:16°C~30°CDB
Indoor unit